Chapter 7 Detailed Explanations of Functional Parameters
Frequency
Set running
frequency
Set reached
frequency
Running command
Multifunctional
output terminal
Cofrequency
range
Time
Frequency
Time
Running command
Accelerating
Decelerating
7: Accelerating
When inverter is in the status of accelerating, this contact is ON.
8: Decelerating
When inverter is in the status of decelerating, this contact is ON.
9. Under voltage alarming
When inverter detects that DC bus voltage is lower than setting
value, this contact is ON and alarm. Under voltage alarming setting
value can be changed through advanced application parameter
group.