Chapter 7 Detailed Explanations of Functional Parameters
0
0
Acceleration/ deceleration time 1
(P107, P108)
1
0
Acceleration/ deceleration time 2
(P401, P402)
0
1
Acceleration/ deceleration time 3
(P403, P404)
1
1
Acceleration/ deceleration time 4
(P405, P406)
15. Frequency increasing signal (Up signal)
When this terminal is valid, the frequency increases at a constant
speed, until operative frequency is highest.
16. Frequency decreasing signal (Down signal)
When this terminal is valid, the frequency decreases at a constant
speed, until operative frequency is lowest.
Attention: Inverter will not memorize the frequency setting changed
by “UP” and “DOWN” signal. When power is turned off and reset
again, inverter still memorizes the set value in P100.
Frequency
Max. running
frequency
Set frequency
Min, running frequency
Running command
UP command
Down command
Time
17: Coasting stop
When this terminal is valid, inverter coasting to stop.
18. Fault reset
Reset the inverter when alarm occurs, this terminal function is same