4. Use a voltmeter (A) to measure the voltage between
the ground (Pin 2) and signal (Pin 3) wires at the AHHC
sensor in the
fl
oat indicator box. Ensure it is at the
high voltage limit for the combine. Refer to Table
Combine Voltage Limits, page 101
.
Figure 3.126: Measuring Voltage at Float
Indicator Box
5. Fully lower the combine feeder house, and
fl
oat the
header up off the down stops (
fl
oat indicator should be
at 4, and the
fl
oat module should be fully separated
from the header).
NOTE:
You may need to hold the HEADER DOWN
switch for a few seconds to ensure the feeder
house is fully lowered.
6. Use a voltmeter (A) to measure the voltage between
the ground and signal wires at the AHHC sensor in the
fl
oat indicator box. It should be at the low voltage limit
for the combine. Refer to Table
7. If the sensor voltage is not within the low and high
limits or if the range between the low and high limits is
insuf
fi
cient, adjust the voltage limits. Refer to
Voltage Limits (One-Sensor System), page 106
.
Figure 3.127: Measuring Voltage at Float
Indicator Box
147831
103
Revision A
Содержание FlexDraper FD1 Series
Страница 2: ...FD1 Series FlexDraper Header for Combines Published April 2016 ...
Страница 3: ...Declaration of Conformity 147831 i Revision A ...
Страница 4: ...147831 ii Revision A ...
Страница 5: ...147831 iii Revision A ...
Страница 6: ...147831 iv Revision A ...
Страница 8: ......
Страница 10: ......
Страница 34: ......
Страница 40: ...PRODUCT OVERVIEW Figure 2 1 Header Width 147831 22 Revision A ...
Страница 189: ...OPERATION Figure 3 260 Flow Chart for Setting the Sensitivity of the Float Optimizer 147831 171 Revision A ...
Страница 462: ......
Страница 484: ......
Страница 508: ......
Страница 509: ......