Table of functions
128
Code
Comm
addr.
Name
Keypad
display
Range
Unit
Default
setting
IM
V
\F
Sl
ip
PM
EL
IM
EL
P
M
Page
PRT_11 780B
Encoder
error
detection
time
EncFaultTime
0.00–
10.00
sec
0.00
○
x x
○
○
○
ELPM:
4.00
PRT_12 780C
Encoder
error
reference
speed
EncFaultPerc
0.0–50.0 %
25.0
○
x x
○
○
○
ELPM:
10.0
PRT_13 780D
Speed
deviation
detection
level
SpdErrLevel
0–100
rpm
IM: 100
○
x x
○
○
○
PM: 20
PRT_14 780E
Speed
deviation
detection
time
SpdErrTime
0–1000
ms
500
○
x x
○
○
○
PRT_15 780F
Overspe
ed error
detection
level
OverSpdLevel
100.0–
130.0
%
110.0
○
x x
○
○
○
PRT_16 7810
Overspe
ed error
detection
time
OverSpd Time
0.00–
2.00
sec
1.00
○
x x
○
○
○
PRT_17 7811
Missing
input
phase
detection
PhInOpenChk
0 (No)
1 (Yes)
0 (No)
○
○
○
○
○
○
PRT_18 7812
Missing
input
phase
detection
voltage
level
Note3)
PhInOpenLvl
2–100
V
3.0
○
○
○
○
○
○
PRT_19 7813
Missing
output
PhOutOpenChk
0 (No)
1 (Yes)
0 (No)
○
○
○
○
○
○
Содержание LSLV-L100 Series
Страница 16: ...3 Preparing the Installation Preparation ...
Страница 36: ...Installing the Inverter 23 Installation Power terminal and control terminal wiring diagram ...
Страница 240: ...Detailed operation by function groups 227 Operation Details BX time FUN_51 set to a value other than 0 ...
Страница 252: ...Detailed operation by function groups 239 Operation Details stops When forward operation has a lighter load ...
Страница 339: ...326 Communication features CAN message frame versions CAN 2 0A CAN 2 0B ...
Страница 395: ...382 ...