75
Performing basic operations
B
asi
c
O
p
e
ra
tion
Parameter setting
Step
Procedure
Function code
Description
1
Set the RUN/STOP
command source
FUN_01
Set Run/Stop Src to “Terminal 1.”
2
Set the speed reference
source
FUN_02
Set Speed Ref Sel to “Analog.”
3
Define analog input
AIO_01
Set Ai1 Define to “Speed Ref.”
4
Define analog input type
AIO_02
Set Ai1 Source to “0 -> 10 V.”
5
Set the speed reference
DIS_01
Adjust the potentiometer to set PreRamp Ref
(DIS_01) to “1500.0 (rpm)”
6
Set acc/dec times
FUN_41
FUN_42
Set the acceleration time (FUN_41) to “10.00
(Sec),” and the deceleration time (FUN_42) to
“20.00 (Sec).”
7
Run FX operation at the
terminal block
-
-
When the FX terminal input is ON, the
inverter accelerates the motor for 10
seconds, and then runs it at 1,500 rpm,
in the forward direction.
-
When the input is OFF, the inverter
decelerates the motor for 20 seconds,
and then stops it.
-
Set SW1 to NPN mode.
8
Run RX operation at the
terminal block
-
-
When the RX terminal input is ON, the
inverter accelerates the motor for 10
seconds, and then runs it at 1,500 rpm,
in the reverse direction.
-
When the input is OFF, the inverter
decelerates the motor for 20 seconds,
and then stops it.
-
Set SW1 to NPN mode.
9
Add-on module
DIS_04
Displays “A/B Pulse.” (Line drive connection)
10
Number of encoder
pulses
PAR_24
Set to “1024.”
11
Encoder direction
PAR_25
Set to “B Phase Lead.”
Содержание LSLV-L100 Series
Страница 16: ...3 Preparing the Installation Preparation ...
Страница 36: ...Installing the Inverter 23 Installation Power terminal and control terminal wiring diagram ...
Страница 240: ...Detailed operation by function groups 227 Operation Details BX time FUN_51 set to a value other than 0 ...
Страница 252: ...Detailed operation by function groups 239 Operation Details stops When forward operation has a lighter load ...
Страница 339: ...326 Communication features CAN message frame versions CAN 2 0A CAN 2 0B ...
Страница 395: ...382 ...