After a normal stop (a status that inverter voltage output becomes OFF after the
stop operation by user settings), the A3 Safety multifunction input terminal
should be ON within the time limit set at [PRT-30 A3 StartTime]. If A3 Safety is
not ON, an "A3 Safety" fault occurs.
If you turn off and then on the inverter power when "A3 Safety" fault has
occurred, the fault status is maintained regardless of the Multifunction input A3
Safety. To turn off the fault, use the keypad reset button or RST of the terminal
block.
The graph below shows the basic movement sequence of A3 Safety.
6.8.15 Fan fault
You can decide the inverter’s inner fan is operating or not according to the user
settings.
Code
Keypad display
Name
Range
Unit
Default setting
PRT-32 FAN Control
FAN operation setting
0 (During Run)
1 (Always ON)
2 (Temp Control)
0 (During Run)
PRT-33 FAN Trip Sel
FAN Trip setting
0 (Trip)
1 (Warning)
1 (Warning)