Detailed operation by function groups
215
O
p
er
ati
o
n
D
etai
ls
If “Free-run” is selected, the motor performs a free-run without deceleration.
If “DC-Brake” is selected, DC voltage is injected into the motor during
deceleration to brake and stop it. This option is available only when the control
mode is set to “V/F”, or “Slip Comp.” Refer to FUN_06–FUN_09 for information
about using the DC brake.
Code
Keypad display
Name
Range
Unit
Default setting
FUN_03 Stop Mode
Stop mode options
0(Decel)
1(Free-run)
2(DC-Brake)
Decel
6.5.3 DC-braking stop (FUN_06–FUN_09)
Codes FUN_06 through FUN_09 are used to set the DC-braking options. When
a stop command is given, the inverter decelerates the motor. During motor
deceleration, when the operation frequency reaches the DC-braking frequency
set at FUN_06, DC voltage is provided to the motor and stops it.
Code
Keypad display
Name
Range
Unit
Default setting
FUN_06 Dcbr Freq
DC braking start
frequency
PAR_12–
PAR_11
Hz
1.00
FUN_07 Dcblk Time
Output block time before
DC braking
0.00–60.00
sec
0.00
FUN_08 Dcbr Value
DC braking amount
0–200
%
10
FUN_09 Dcbr Time
DC braking time
0.0–60.0
sec
1.0
Содержание LSLV-L100 Series
Страница 16: ...3 Preparing the Installation Preparation ...
Страница 36: ...Installing the Inverter 23 Installation Power terminal and control terminal wiring diagram ...
Страница 240: ...Detailed operation by function groups 227 Operation Details BX time FUN_51 set to a value other than 0 ...
Страница 252: ...Detailed operation by function groups 239 Operation Details stops When forward operation has a lighter load ...
Страница 339: ...326 Communication features CAN message frame versions CAN 2 0A CAN 2 0B ...
Страница 395: ...382 ...