6.2.4.3 Running static auto-tuning for induction motors
Preparation
Before running a static auto-tuning, fix the motor axis so that it won’t move during
the auto-tuning. Accurate values can be obtained only when the motor axis is in
a static condition.
Setting the parameters for auto-tuning
Code
Keypad display
Name
Range
Setting
PAR_31 AutoTuneType
Auto-tuning options
0 (Rotational)
1 (StandStill)
1 (StandStill)
PAR_41 IM AutoTune
Induction motor auto-tuning
option
0 (None)
1 (ALL1)
4 (Rs Tuning)
5 (Lsigma)
8 (If/Tr/Ls Tune)
0 (None)
The L100 inverter provides 4 different types of static auto-tuning. The “ALL1”
type auto-tuning detects stator resistance (Rs), leakage factor (Lsigma), If, stator
inductance (Ls), rotor time constant (Tr) - it does not perform a test on the
encoder or an inertia tuning.