Detailed operation by function groups
205
O
p
er
ati
o
n
D
etai
ls
for the time set at AIO_37 (Time Out), the inverter decides that the analog input
command is lost.
For multifunction analog input lost command conditions and the decision time,
refer to
6.4 Analog input and output (AIO) group
on page
If the inverter operation is stopped due to a lost command, the inverter does not
restart automatically when the lost command condition is released. If the inverter
is run by terminal block inputs, the forward operation command must be turned
off, and then turned on again for the operation to begin again. If it is run by the
keypad, the FWD or REV keys must be pressed again.
Code
Keypad display
Function
Unit
Description
Range
AIO_38
Lost Command
0 (None)
-
Continue operation when a multifunction
analog input lost command happens.
1(Free-run)
-
Perform a free-run stop when a
multifunction analog input lost command
happens.
2 (Decel)
-
Perform a deceleration stop when a multi-
function analog input lost command
happens.
When a lost command takes place, an “LOAI [input terminal #]” message is
displayed on the keypad. The percentage value in the second line shows the
analog input value. Adjust this value to make it stay out of range of the lost
command conditions to make the message disappear and change the status of
the inverter operable.
[V/F,
Slip Comp mode]
[Speed(IM) mode]
Содержание LSLV-L100 Series
Страница 16: ...3 Preparing the Installation Preparation ...
Страница 36: ...Installing the Inverter 23 Installation Power terminal and control terminal wiring diagram ...
Страница 240: ...Detailed operation by function groups 227 Operation Details BX time FUN_51 set to a value other than 0 ...
Страница 252: ...Detailed operation by function groups 239 Operation Details stops When forward operation has a lighter load ...
Страница 339: ...326 Communication features CAN message frame versions CAN 2 0A CAN 2 0B ...
Страница 395: ...382 ...