Table of functions
129
Func
tion
T
a
bl
e
Code
Comm
addr.
Name
Keypad
display
Range
Unit
Default
setting
IM
V
\F
Sl
ip
PM
EL
IM
EL
P
M
Page
phase
detection
PRT_20 7814
Overload
warning
level
OL Level
30–250
%
150
○
○
○
○
○
○
PRT_21 7815
Overload
warning
time
OL Time
0–30
sec
10
○
○
○
○
○
○
PRT_22 7816
Overload
fault trip
options
OLT Select
0 (No) / 1
(Yes)
1 (Yes)
○
○
○
○
○
○
PRT_23 7817
Overload
fault trip
level
Note4)
OLT Level
30–250
%
180
○
○
○
○
○
○
PRT_24 7818
Overload
fault trip
time
Note4)
OLT Time
0–60
sec
30
○
○
○
○
○
○
PRT_25 7819
Inverter
overheat
detection
temperat
ure
Note5)
IH Warn
Temp
50 – 110 deg 95
○
○
○
○
○
○
PRT_26 781A
Inverter
overheat
detection
band
IH Warn
Band
0–10
deg 5
○
○
○
○
○
○
PRT_27 781B
Motor
overheat
detection
temperat
ure
MH Warn
Temp
75–130
deg 120
○
○
○
○
○
○
PRT_28 781C
Motor
overheat
detection
temperat
MH Warn
Band
0–10
deg 5
○
○
○
○
○
○
Содержание LSLV-L100 Series
Страница 16: ...3 Preparing the Installation Preparation ...
Страница 36: ...Installing the Inverter 23 Installation Power terminal and control terminal wiring diagram ...
Страница 240: ...Detailed operation by function groups 227 Operation Details BX time FUN_51 set to a value other than 0 ...
Страница 252: ...Detailed operation by function groups 239 Operation Details stops When forward operation has a lighter load ...
Страница 339: ...326 Communication features CAN message frame versions CAN 2 0A CAN 2 0B ...
Страница 395: ...382 ...