Detailed operation by function groups
196
The following table lists the functions available for multifunction analog input
terminals.
Code
Keypad display
Function
Range
Unit
Description
AIO_01 Ai1 Define
Define multifunction
analog input Ai1
0 (Not Used)
1 (Speed Ref)
6 (Torque Bias)
Defines types of
multifunction analog
input Ai1 (V1).
AIO_02 Ai1 Source
Input source for
multifunction
analog input Ai1
0 (0 – 10 V)
1 (10 – 0 V)
2 (-10 – 10 V)
3 (10 – -10 V)
Defines input options of
multifunction analog
input Ai1 (V1).
AIO_03 Ai1 In X1
Minimum value for
multifunction
analog input Ai1
AIO_07
–AIO_05
%
Sets the minimum
amount of analog Input
(based on 0 V input).
AIO_04 Ai1 Out Y1
Minimum input bias
for multifunction
analog input Ai1
AIO_08
–AIO_06
%
Defines the value set at
AIO_01 based on the
analog input at AIO_03
AIO_05 Ai1 In X2
Maximum input for
multifunction
analog input Ai1
0.00–100.00
%
Defines the maximum
input value for analog
input.
AIO_06 Ai1 Out Y2
Maximum input
gain for
multifunction
analog input Ai1
0.00–250.00
%
Defines the value set at
AIO_01 based on the
analog input at AIO_05.
Содержание LSLV-L100 Series
Страница 16: ...3 Preparing the Installation Preparation ...
Страница 36: ...Installing the Inverter 23 Installation Power terminal and control terminal wiring diagram ...
Страница 240: ...Detailed operation by function groups 227 Operation Details BX time FUN_51 set to a value other than 0 ...
Страница 252: ...Detailed operation by function groups 239 Operation Details stops When forward operation has a lighter load ...
Страница 339: ...326 Communication features CAN message frame versions CAN 2 0A CAN 2 0B ...
Страница 395: ...382 ...