Troubleshooting
352
Fault
Cause
Remedy
Parameters cannot
be set.
The inverter is running (driving mode).
Stop the inverter, switch to program
mode and set the parameter.
The password is incorrect.
Confirm the password, disable the
parameter lock, and then set the
parameter.
The motor is not
rotating.
The emergency stop signal is activated.
Reset the emergency stop (BX).
The operating command is set
incorrectly.
Check the operating command
setting.
The control circuit connections are
incorrect.
Check the control circuit connections.
The frequency command is set
incorrectly.
Check the frequency command
setting.
The input voltage or current for the
frequency is incorrect.
Check the input voltage or current for
the frequency.
The PNP/NPN mode is selected
incorrectly.
Check the PNP/NPN mode setting.
[STOP] is pressed.
Check that the inverter is in a normal
condition and resume operation.
Motor torque is too low.
Increase the torque limit to allow the
inverter to accelerate or decelerate to
the rated value.
The motor rotates
in the opposite
direction to the
command.
The inverter’s output connections for the
motor are incorrect.
Check the inverter’s output
connections.
The forward/reverse rotation control
circuit connections between the inverter
and the control panel are incorrect.
Check the forward/reverse rotation
control circuit connections.
The motor is
overheating.
The load is too heavy.
Reduce the load.
Increase the Acc/Dec time.
Содержание LSLV-L100 Series
Страница 16: ...3 Preparing the Installation Preparation ...
Страница 36: ...Installing the Inverter 23 Installation Power terminal and control terminal wiring diagram ...
Страница 240: ...Detailed operation by function groups 227 Operation Details BX time FUN_51 set to a value other than 0 ...
Страница 252: ...Detailed operation by function groups 239 Operation Details stops When forward operation has a lighter load ...
Страница 339: ...326 Communication features CAN message frame versions CAN 2 0A CAN 2 0B ...
Страница 395: ...382 ...