Table of functions
112
5.6 Control (CON) group
Code
Comm
addr.
Name
Keypad
display
Range
Unit
Default
setting
IM
V
\F
Sl
ip
PM
EL
IM
EL
P
M
Page
CON_00 -
Jump to
codes
Jump
Code
1–92
1
○
○
○
○
○
○
CON_02 7602
Speed
controller
gain ratio
ASR PI
Ratio
1.0–500.0
%
20.0
x x x
○
x
○
CON_03 7603
Speed
controller
proportion
al gain 1
ASR P
Gain1
0.1–999.9
%
IM: 50.0
○
x x
○
○
○
PM:
100.0
CON_04 7604
Speed
controller
integral
time 1
ASR I
Gain1
0–50000
ms
IM: 300
○
x x
○
○
○
PM: 50
CON_05 7605
Speed
controller
input LPF
time
constant 1
ASR
LPF1
0–20000
ms
0
○
x x
○
○
○
CON_06 7606
Speed
controller
proportion
al gain 2
ASR P
Gain2
0.1–500.0
%
IM: 50.0
○
x x
○
○
○
PM:
100.0
CON_07 7607
Speed
controller
integral
time 2
ASR I
Gain2
0–50000
ms
IM: 300
○
x x
○
○
○
PM: 50