6.8.7 Speed deviation error settings
Speed deviation errors output an error signal when a deviation occurs between
the command speed and the true motor speed. The deviation must be present
for longer than the duration set at PRT_14 (Speed deviation detection time) and
more than the speed set at PRT_13 (speed deviation detection level that is
calculated as a percentage of PAR_14 [Motor sync speed]). The default settings
that are used depend on the type of motor.
Code
Keypad display
Name
Range
Unit
Default setting
PRT_13 SpdErrLevel
Detection level of speed
deviation
0–100
rpm
Asynch: 100
Synch: 20
PRT_14 SpdErrTime
Detection time speed
deviation
0–1000
ms
500