Type
Model
Unit
kW
Cooling Capacity kcal/h
Btu/h
kW
Heating Capacity kcal/h
Btu/h
Casing
Dimensions(WxHxD)
Body
mm
inch
Coil Rows x Columns x FPI
Face Area m
2
Type
Motor Output x Number W
Running Current A
Fan Air Flow Rate(H / M / L) CMM
cfm
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side mm(inch)
Pipe Connections Gas Side mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L) dB(A)
Power Supply Ø, V, Hz
Refrigerant Control
Transmission cable mm
2
Floor Standing
ARNU07GCEU4 ARNU09GCEU4 ARNU12GCEU4
2.2 2.8 3.6
1,900 2,400 3,100
7,500 9,600 12,300
2.5 3.2 4.0
2,200 2,800 3,400
8,500 10,900 13,600
Galvanized Galvanized Galvanized
Steel Plate Steel Plate Steel Plate
978 x 639 x 190 978 x 639 x 190 978 x 639 x 190
38-1/2 x 25-5/32 x 7-15/32 38-1/2 x 25-5/32 x 7-15/32 38-1/2 x 25-5/32 x 7-15/32
2 x 12 x 19 2 x 12 x 19 2 x 12 x 19
0.16 0.16 0.16
Sirocco Fan Sirocco Fan Sirocco Fan
19 x 1, 5 x 1 19 x 1, 5 x 1 19 x 1, 5 x 1
0.76 0.76 0.76
8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5
300 / 265 / 229 335 / 300 / 265 371 / 335 / 300
Direct Direct Direct
BLDC BLDC BLDC
Microprocessor, Microprocessor, Microprocessor,
Thermostat for Thermostat for Thermostat for
cooling and heating cooling and heating cooling and heating
Foamed polystrene Foamed polystrene Foamed polystrene
Resin Net(washable) Resin Net(washable) Resin Net(washable)
Fuse Fuse Fuse
Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4)
Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2)
12(15/32) 12(15/32) 12(15/32)
20(44.1) 20(44.1) 20(44.1)
35 / 33 / 31 36 / 34 / 32 37 / 35 / 33
1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
1, 220, 60 1, 220, 60 1, 220, 60
EEV EEV EEV
CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Notes:
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be
considered for electrical work and design. Especially the power cable and circuit breaker should be selected in accordance
with that.
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
Floor Standing
_
3
2. Specification
Indoor unit
Indoor Units
Содержание ARNU48GBRZ4
Страница 1: ...Indoor unit R410A 0CVP0 03A Replaces 0CVP0 02A P No MFL55028429 ...
Страница 2: ...Indoor unit Introduction General Information Indoor Units Dip Switch Group Control Setting ...
Страница 353: ...Indoor unit 6 _ Fresh Air Intake Unit Indoor Units 5 Wiring Diagrams BR Chassis B8 Chassis ...