Indoor unit
2
_
Ceiling Cassette 4-way(2)
Indoor Units
2. Specifications
* Model Name
A:Basic, C:Plasma
Model
Unit
kW
Cooling Capacity kcal/h
Btu/h
kW
Heating Capacity kcal/h
Btu/h
Casing
Body
mm
Dimensions(WxHxD)
inch
Front Panel
mm
inch
Coil Rows x Columns x FPI
Face Area m
2
Type
Motor Output x Number W
Running Current A
Fan
Air Flow Rate(H / M / L)
CMM
cfm
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side mm(inch)
Pipe Connections Gas Side mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight Body kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L) dB(A)
Power Supply Ø, V, Hz
Refrigerant Control
Transmission cable mm
2
Panel Color
Panel Name(Accessory)
Elevation Grill(Accessory)
ARNU07GTN*4 ARNU15GTN*4 ARNU18GTN*4
2.2 4.5 5.6
1,900 3,900 4,800
7,500 15,400 19,100
2.5 5.0 6.3
2,200 4,300 5,400
8,500 17,100 21,500
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
840 x 246 x 840 840 x 246 x 840 840 x 246 x 840
33-1/16 x 9-11/16 x 33-1/16 33-1/16 x 9-11/16 x 33-1/16 33-1/16 x 9-11/16 x 33-1/16
950 x 25 x 950 950 x 25 x 950 950 x 25 x 950
37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
2 x 10 x 19 2 x 10 x 19 2 x 10 x 19
0.57 0.57 0.57
Turbo Fan Turbo Fan Turbo Fan
135 135 135
0.56 0.56 0.56
13 / 12 / 11 15 / 13 / 12 16 / 14 / 12
459 /424 / 388 530 /459 / 424 565 / 530 / 424
Direct Direct Direct
BLDC BLDC BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene Foamed polystrene
Fuse Fuse Fuse
Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8)
Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8)
25(1) 25(1) 25(1)
23.5(51.8) 23.5(51.8) 23.5(51.8)
29 / 26 / 24 32 / 29 / 26 34 / 30 / 26
1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
1, 220, 60 1, 220, 60 1, 220, 60
EEV EEV EEV
CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C
Morning fog Morning fog Morning fog
PT-UMC PT-UMC PT-UMC
PTEGM0 PTEGM0 PTEGM0
Notes:
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics”
chapter should be considered for electrical work and design. Especially the power cable and circuit breaker
should be selected in accordance with that.
5. EEV: Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
Содержание ARNU48GBRZ4