7. External Static Pressure (E.S.P) & Air Flow
Indoor unit
22
_
Ceiling Concealed Duct(Middle Static)
Indoor Units
Note:
1. The above table shows the correlation between the air rates and E.S.P.
2. The above table shows the available E.S.P. range.
3. If the E.S.P. of the installed indoor is less than the lowest value(as mention in the table), indoor components
can be failed.
ARNU28GM2A4, ARNU36GM2A4
(Unit: CMM)
Setting value
Static Pressure (mmAq(Pa))
4(39)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
85
24.9
-
-
-
-
-
-
90
27.6
22.7
-
-
-
-
-
95
30.4
25.7
20.7
-
-
-
-
100
33.1
28.7
24.0
-
-
-
-
105
35.9
31.7
27.3
20.8
-
-
-
110
38.6
34.7
30.5
24.3
20.6
-
-
115
-
37.8
33.8
27.9
23.8
-
-
120
-
-
37.1
31.4
27.0
22.4
20.5
125
-
-
-
35.0
30.1
25.7
23.7
130
-
-
-
37.1
32.0
27.6
25.7
ARNU28GM2A4, ARNU36GM2A4
Fan Performance
90 SV
100 SV
110 SV
120 SV
130 SV
16
14
12
10
8
6
4
External Static Pressure(mm.Aq)
20.0 22.0 24.0 26.0 28.0 30.0 32.0 34.0 36.0 38.0 40.0
Air Flow (CMM)