9. Sound Levels
Indoor Units
Overall
9.1 Sound Pressure Levels
1.5m
1.5m
With Case
Microphone
❈
Measuring place : Anechoic chamber
Model
Sound Pressure Levels dB(A)
H
M
L
ARNU07GCEA4 ARNU07GCEA4
35
33
31
ARNU09GCEA4 ARNU09GCEA4
36
34
32
ARNU12GCEA4 ARNU12GCEA4
37
35
33
ARNU15GCEA4 ARNU15GCEA4
38
37
35
ARNU18GCFA4 ARNU18GCFA4
40
37
34
ARNU24GCFA4 ARNU24GCFA4
43
40
37
Notes:
1. Sound measured at 1.5m away from the center of the unit
2. Operating condition|
- Power source : 220-240V 50Hz / 220V 60Hz
- Cooling : Indoor temperature (27°C DB, 19°C WB),
Outdoor temperature (35°C DB, 24°C WB)
- Heating : Indoor temperature (20°C DB, 15°C WB),
Outdoor temperature (7°C DB, 6°C WB)
3. Reference accoustic pressure 0dB = 20μPa
4. Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment in installed.
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500
1000
2000
4000
8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500
1000
2000
4000
8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500
1000
2000
4000
8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
ARNU07GCEA4
ARNU07GCEU4
ARNU09GCEA4
ARNU09GCEU4
ARNU12GCEA4
ARNU12GCEU4
Содержание ARNU48GBRZ4
Страница 1: ...Indoor unit R410A 0CVP0 03A Replaces 0CVP0 02A P No MFL55028429 ...
Страница 2: ...Indoor unit Introduction General Information Indoor Units Dip Switch Group Control Setting ...
Страница 353: ...Indoor unit 6 _ Fresh Air Intake Unit Indoor Units 5 Wiring Diagrams BR Chassis B8 Chassis ...