Indoor unit
ARTCOOL (Gallery)
_
9
Indoor Units
Symbols:
MCA: Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA ≤ 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA.
5. Instead of fuse, use Circuit Breaker.
Units
Model
Type
Hz
Volts
Voltage Range
ARNU07GSF14
SF
Max:264
0.23
15
0.024
0.18
35
35
ARNU09GSF14
SF
50
220 - 240
Min:198
0.23
15
0.024
0.18
35
35
ARNU12GSF14
SF
0.23
15
0.024
0.18
35
35
ARNU07GSF14
SF
Max:242
0.23
15
0.024
0.18
35
35
ARNU09GSF14
SF
60
220
Min:198
0.23
15
0.024
0.18
35
35
ARNU12GSF14
SF
0.23
15
0.024
0.18
35
35
Power Supply
IFM
Input(W)
MCA
MFA
kW
FLA
Cooling Heating
8. Electric Characteristics