Indoor unit
Ceiling Concealed Duct (High Sensible)
_
23
Indoor Units
7. External Static Pressure (E.S.P) & Air Flow
Note:
1. The above table shows the correlation between the air rates and E.S.P.
2. The above table shows the available E.S.P. range.
3. If the E.S.P. of the installed indoor is less than the lowest value(as mention in the table), indoor components
can be failed.
ARNU36GB8A4, ARNU42GB8A4, ARNU48GB8A4
(Unit: CMM)
Setting Value
Static Pressure(mmAq(Pa))
6(59)
9(88)
12(118)
15(147)
18(176)
20(196)
22(216)
23(226)
25(245)
60
40.5
-
-
-
-
-
-
-
-
65
52.7
39.3
-
-
-
-
-
-
-
70
63.7
47.1
-
-
-
-
-
-
-
75
71.1
56.9
44.7
-
-
-
-
-
-
80
76.3
69.7
55.2
-
-
--
-
-
-
85
83.3
78.6
67.4
55.9
31.8
-
-
-
-
91
89.7
87.1
78.9
67.6
54.2
-
-
-
-
95
93.4
91.4
86.1
77.0
66.4
50.6
30.0
-
-
100
93.4
91.4
88.3
84.9
75.9
69.5
60.8
43.1
-
105
93.2
91.3
88.3
84.9
81.1
77.4
69.2
67.9
51.3