2. Specifications
Indoor unit
4
_
Ceiling Concealed Duct(Low Static)
Indoor Units
Notes:-
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should
be considered for electrical work and design. Especially the power cable and circuit breaker should be selected in
accordance with that.
4. EEV : Electronic Expansion Valve
5. Sound pressure levels are measured at 20Pa External Static Pressure condition.
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
Type
Model
Unit
kW
Cooling Capacity kcal/h
Btu/h
kW
Heating Capacity kcal/h
Btu/h
Casing
Dimensions(WxHxD) Body
mm
inch
Coil Rows x Columns x FPI
Face Area m
2
Type
Motor Output x Number W
Running Current A
Air Flow Rate(H / M / L) CMM
(High Mode-factory set) cfm
Fan External Static Pressure mmAq(Pa)
Air Flow Rate(H / M / L) CMM
(Standard Mode) cfm
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side mm(inch)
Pipe Connections Gas Side mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight kg(lbs)
Noise Level (Sound Pressure, 1.5m, H/M/L) dB(A)
Power Supply Ø, V, Hz
Refrigerant Control
Transmission cable mm
2
Ceiling Concealed Duct (Low Static)
ARNU21GL3G4 ARNU24GL3G4
6.2 7.1
5,300 6,100
21,000 24,000
7.0 8.0
6,000 6,900
23,900 27,300
Galvanized Steel Plate Galvanized Steel Plate
1,100 × 190 × 700 1,100 × 190 × 700
43-5/16 × 7-15/32 × 27-9/16 43-5/16 × 7-15/32 × 27-9/16
2 x 11 x 18 2 x 11 x 18
0.21 0.21
Sirocco Fan Sirocco Fan
19 x 2 19 x 2
0.97 0.97
17.5 / 14.0 / 12.0 20.0 / 16.0 / 12.0
620 / 500 / 430 710 / 570 / 430
2.54 (25) 2.54 (25)
17.5 / 14.0 / 12.0 20.0 / 16.0 / 12.0
620 / 500 / 430 710 / 570 / 430
0 (0) 0 (0)
Direct Direct
BLDC BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene
- -
Fuse Fuse
Ø9.52(3/8) Ø9.52(3/8)
Ø15.88(5/8) Ø15.88(5/8)
25.4(1) 25.4(1)
27 (59.5) 27 (59.5)
35 / 29 / 28 36 / 33 / 28
1, 220 - 240, 50 1, 220 - 240, 50
1, 220, 60 1, 220, 60
EEV EEV
1.0~1.5 x 2C 1.0~1.5 x 2C