Indoor unit
2. Wall Mounted, ART COOL Gallery, ART COOL Mirror
Dip Switch & Group Control Setting
_
9
Dip Switch &
Group Control Setting
Master
Slave
Slave
Display Error Message
Only connect serial signal and
GND lines between indoor units.
or
LGAP Network System
Master
GND
Signal
12 V
Slave
2.2 Group Control 1
(1) Group Control 1
n
Wired remote controller 1 + Standard Indoor Units
Group Control Setting
- This function is only for group control.
- Please don’t set this function in case of non-group control.
- This function is the Master or Slave setting function of indoor unit
- Set only one indoor unit to Master, set the others to slave.
- After setting Group Control of the product, turn off the power then turn it back on after 1 minute.
- Master checking whether the buzzer sounds, such as indoor rings below.
▶
Master: “Beep” (Buzzer sound 1 time)
▶
Slave: “Beep, Beep, Beep, Beep, Beep ” (Buzzer sounds 5 times)
1. It is possible to 16 indoor units(Max) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. You can connect all the types of 2nd generation indoor units .
3. It is possible to use wireless remote controller at the same time.