7. External Static Pressure (E.S.P) & Air Flow
Indoor unit
24
_
Ceiling Concealed Duct (High Sensible)
Indoor Units
ARNU07GBGA4, ARNU09GBGA4, ARNU12GBGA4, ARNU15GBGA4
Capacity
Mode
Set value
Standard
ESP(mmAq(Pa))
CMM
Lower Limit of External
Static Pressure(mmAq(Pa))
Upper Limit of External
Static Pressure(mmAq(Pa))
7k
High
(factory set)
HI
98
6(59)
12.5(441)
6(59)
12(118)
Mid
95
11.5(406)
Low
92
9.4(332)
Standard
HI
92
4(39)
14.6(516)
4(39)
8(78)
Mid
89
13.7(484)
Low
86
12.3(434)
9k
High
(factory set)
HI
99
6(59)
12.8(452)
6(59)
12(118)
Mid
95
11.5(406)
Low
92
9.4(332)
Standard
HI
93
4(39)
15.1(533)
4(39)
8(78)
Mid
89
13.7(484)
Low
86
12.3(434)
12k
High
(factory set)
HI
100
6(59)
13.5(477)
6(59)
12(118)
Mid
96
12.1(427)
Low
93
9.4(332)
Standard
HI
95
4(39)
16.6(586)
4(39)
8(78)
Mid
92
15.1(533)
Low
89
13.7(483)
15k
High
(factory set)
HI
128
8(78)
13.8(487)
8(78)
18(177)
Mid
106
11.8(417)
Low
103
8.3(293)
Standard
HI
100
6(59)
13.5(477)
6(59)
10(98)
Mid
94
12.1(427)
Low
89
9.0(318)
Note:
1.The above table shows the available E.S.P. range.
2. The air flow of above model is increased by 20% depending on the Mode setting.
3. Above models are developed for high efficiency and high sensible heat.
If you want to use Zone control, you have to set ESP Value.