Ceiling Concealed Duct(Low Static)
Indoor Units
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where
voltage supplied to unit terminals is not below or above
the listed range limits,
2. Maximum allowable voltage unbalance between phas-
es is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Units
Model Type Hz Volts Voltage Range
ARNU05GL1G4 L1 0.50 15 0.019 0.40 40 40
ARNU07GL1G4 L1 0.50 15 0.019 0.40 40 40
ARNU09GL1G4 L1 0.50 15 0.019 0.40 40 40
ARNU12GL2G4 L2 1.00 15 0.024 0.76 85 85
ARNU15GL2G4 L2 1.00 15 0.024 0.76 85 85
ARNU18GL2G4 L2 1.00 15 0.024 0.76 85 85
ARNU21GL3G4 L3 1.20 15 0.038 0.97 115 115
ARNU24GL3G4 L3 1.20 15 0.038 0.97 115 115
ARNU05GL1G4 L1 0.50 15 0.019 0.40 40 40
ARNU07GL1G4 L1 0.50 15 0.019 0.40 40 40
ARNU09GL1G4 L1 0.50 15 0.019 0.40 40 40
ARNU12GL2G4 L2 1.00 15 0.024 0.76 85 85
ARNU15GL2G4 L2 1.00 15 0.024 0.76 85 85
ARNU18GL2G4 L2 1.00 15 0.024 0.76 85 85
ARNU21GL3G4 L3 1.20 15 0.038 0.97 115 115
ARNU24GL3G4 L3 1.20 15 0.038 0.97 115 115
Power Supply
IFM
Input(W)
MCA
MFA
kW
FLA
Cooling Heating
50
220-240
Max:264
Min:198
60
220
Max:242
Min:198
Indoor unit