Indoor unit
26
_
Ceiling Concealed Duct (High Sensible)
Indoor Units
8. Electric Characteristics
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above the listed range
limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Unit
Power Supply
IFM
Input(W)
Model
Type
Hz
Volts
Voltage
Range
MCA
MFA
kW
FLA
cooling
Heating
ARNU07GBGA4
BG
50
220-240
Max:264
Min:198
3.31
15
0.35
2.65
450
450
ARNU09GBGA4
BG
3.31
15
0.35
2.65
450
450
ARNU12GBGA4
BG
3.31
15
0.35
2.65
450
450
ARNU15GBGA4
BG
3.31
15
0.35
2.65
450
450
ARNU18GBRA4
BR
4.40
15
0.37
3.50
450
450
ARNU07GBGA4
BG
60
220
Max:242
Min:198
3.31
15
0.35
2.65
450
450
ARNU09GBGA4
BG
3.31
15
0.35
2.65
450
450
ARNU12GBGA4
BG
3.31
15
0.35
2.65
450
450
ARNU15GBGA4
BG
3.31
15
0.35
2.65
450
450
ARNU18GBRA4
BR
4.40
15
0.37
3.50
450
450
ARNU24GBRA4
BR
4.40
15
0.37
3.50
450
450
ARNU28GBRA4
BR
4.40
15
0.37
3.50
450
450
ARNU36GB8A4
B8
6.50
15
0.75
5.20
800
800
ARNU42GB8A4
B8
6.50
15
0.75
5.20
800
800
ARNU48GB8A4
B8
6.50
15
0.75
5.20
800
800
ARNU24GBRA4
BR
4.40
15
0.37
3.50
450
450
ARNU28GBRA4
BR
4.40
15
0.37
3.50
450
450
ARNU36GB8A4
B8
6.50
15
0.75
5.20
800
800
ARNU42GB8A4
B8
6.50
15
0.75
5.20
800
800
ARNU48GB8A4
B8
6.50
15
0.75
5.20
800
800