Indoor unit
2. Specifications
Ceiling Concealed Duct(Middle Static)
_
3
Indoor Units
Notes:
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics”
chapter should be considered for electrical work and design. Especially the power cable and circuit breaker
should be selected in accordance with that.
4. EEV : Electronic Expansion Valve
5. Sound pressure levels are measured at 50Pa External Static Pressure condition.
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
Type
Model
Unit
kW
Cooling Capacity kcal/h
Btu/h
kW
Heating Capacity kcal/h
Btu/h
Casing
Dimensions(WxHxD) Body
mm
inch
Coil Rows x Columns x FPI
Face Area m
2
Type
Motor Output x Number W
Running Current A
Air Flow Rate(H / M / L) CMM
(High Mode-factory set) cfm
Fan External Static Pressure mmAq(Pa)
Air Flow Rate(H / M / L) CMM
(Standard Mode) cfm
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side mm(inch)
Pipe Connections Gas Side mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight Body kg(lbs)
Noise Level(Sound Pressure, 1.5m, H / M / L) dB(A)
Power Supply Ø, V, Hz
Refrigerant Control
Transmission Cable mm
2
Ceiling Concealed Duct - Middle Static
ARNU15GM1A4 ARNU18GM1A4 ARNU24GM1A4
4.5 5.6 7.1
3,900 4,800 6,100
15,400 19,100 24,200
5.0 6.3 8.0
4,300 5,400 6,900
17,100 21,500 27,300
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
900 × 270 × 700 900 × 270 × 700 900 × 270 × 700
35-7/16 x 10-5/8 x 27-9/16 35-7/16 x 10-5/8 x 27-9/16 35-7/16 x 10-5/8 x 27-9/16
2 x 13 x 18 2 x 13 x 18 3 x 13 x 18
0.21 0.21 0.21
Sirocco Fan Sirocco Fan Sirocco Fan
136 x 1 136 x 1 136 x 1
1.6 1.6 1.6
16.0 / 12.0 / 9.0 17.0 / 14.5 / 12.0 19.0 / 16.0 / 14.0
565 / 424 / 318 600 / 512 / 424 671 / 565 / 494
6(59) 6(59) 6(59)
16.0 / 12.0 / 9.0 17.0 / 14.5 / 12.0 19.0 / 16.0 / 14.0
565 / 424 / 318 600 / 512 / 424 671 / 565 / 494
2.5(25) 2.5(25) 2.5(25)
Direct Direct Direct
BLDC BLDC BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene Foamed polystrene
- - -
Fuse Fuse Fuse
Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8)
Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8)
25(1) 25(1) 25(1)
25.5(56) 25.5(56) 26.5(58)
30 / 27 / 23 31 / 28 / 25 32 / 29 / 26
1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
1, 220, 60 1, 220, 60 1, 220, 60
EEV EEV EEV
CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Содержание ARNU48GBRZ4
Страница 1: ...Indoor unit R410A 0CVP0 03A Replaces 0CVP0 02A P No MFL55028429 ...
Страница 2: ...Indoor unit Introduction General Information Indoor Units Dip Switch Group Control Setting ...
Страница 353: ...Indoor unit 6 _ Fresh Air Intake Unit Indoor Units 5 Wiring Diagrams BR Chassis B8 Chassis ...