Indoor unit
9. Sound Levels
Ceiling Concealed Duct_Built in (Low Static)
_
15
Indoor Units
Overall
9.1 Sound Pressure Levels
1.5m
Ceiling
2.0m
Microphone
❈
Measuring place : Anechoic chamber
Model
Sound Pressure Levels dB(A)
H
M
L
ARNUPBSGB30(Acc'y), PBSC30(Acc'y)
33
32
29
ARNUPBSGB30(Acc'y), PBSC30(Acc'y)
34
33
32
ARNUPBSGB30(Acc'y), PBSC30(Acc'y)
35
34
33
ARNUPBSGB30(Acc'y), PBSC30(Acc'y)
41
40
37
ARNUPBSGB40(Acc'y), PBSC40(Acc'y)
43
40
37
ARNUPBSGB40(Acc'y), PBSC40(Acc'y)
46
43
37
Notes:
1. Sound measured at 1.5m away from the center of the unit
2. Operating condition|
- Power source : 220-240V 50Hz / 220V 60Hz
- Cooling : Indoor temperature (27°C DB, 19°C WB),
Outdoor temperature (35°C DB, 24°C WB)
- Heating : Indoor temperature (20°C DB, 15°C WB),
Outdoor temperature (7°C DB, 6°C WB)
3. Reference accoustic pressure 0dB = 20μPa
4. Sound level will vary depending on a range of factors such
as the construction(acoustic absorption coefficient) of par-
ticular room in which the equipment in installed.
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500
1000
2000
4000
8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500
1000
2000
4000
8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500
1000
2000
4000
8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
ARNUPBSGB30
(Acc'y), PBSC30(Acc'y)
ARNUPBSGB30
(Acc'y), PBSC30(Acc'y)
ARNUPBSGB30
(Acc'y), PBSC30(Acc'y)
Содержание ARNU48GBRZ4
Страница 1: ...Indoor unit R410A 0CVP0 03A Replaces 0CVP0 02A P No MFL55028429 ...
Страница 2: ...Indoor unit Introduction General Information Indoor Units Dip Switch Group Control Setting ...
Страница 353: ...Indoor unit 6 _ Fresh Air Intake Unit Indoor Units 5 Wiring Diagrams BR Chassis B8 Chassis ...