Indoor unit
Ceiling Concealed Duct(Low Static)
_
7
Indoor Units
5. Wiring Diagrams
CONNECTOR NUMBER SPEC.
DESCRIPTION
CN-MOTOR1 Fan motor output Motor output of BLDC
CN-MOTOR2 Fan motor output Motor output of BLDC
CN-PIPE_OUT Discharge pipe sensor Pipe out thermistor
CN-PIPE_IN Suction pipe sensor Pipe in thermistor
CN-ROOM Room sensor Room thermistor
CN-REMO Remote controller Remote control line
CN-FLOAT Float switch input Float switch sensing
CN-EEV EEV output EEV control output
CN-D_PUMP Drain pump output AC output for drain pump
CN-OPTION Option PWB. Communication between main and option
CN-COM Communication Communication between indoor and outdoor
CN-POWER AC power supply AC power line input for indoor controller
CN-ZONE Zone Controller Zone control line
CN-DISPLAY RF Remote controller RF remote control line
CN-CC Dry contact Dry contact line
CN-EXT External On/Off External On/Off signal input
L1 Chassis
CAUTION
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Function
Description
Setting Off
Setting On
Default
SW1
Communication
N/A (Default)
-
-
Off
SW2
Cycle
N/A (Default)
-
-
Off
SW3
Group Control
Selection of Master or Slave
Master
Slave
Off
SW4
Dry Contact Mode
Selection of Dry Contact Mode
Wired/Wireless remote controller selec-
tion of Manual or Auto operation Mode
Auto
Off
SW5
Installation
Fan continuous operation
Continuous operation Removal
-
Off
SW6
Heater linkage
N/A
-
-
Off
SW7
Ventilator linkage
Selection of Ventilator linkage
Linkage Removal
Working
Off
Vane selection (Console)
Selection of up/down side Vane
Up side + Down side Vane
Up side Vane Only
Region selection
Selection tropical region
General model
Tropical model
SW8
Etc.
Spare
-
-
Off