2. Specifications
Indoor unit
2
_
Ceiling Cassette 1-Way
Indoor Units
Type
Model
Unit
kW
Cooling Capacity kcal/h
Btu/h
kW
Heating Capacity kcal/h
Btu/h
Casing
Body
mm
Dimensions (WxHxD)
inch
Front Panel
mm
inch
Coil Rows x Columns x FPI
Face Area m
2
Type
Motor Output x Number W
Running Current A
Fan Air Flow Rate(H / M / L) CMM
cfm
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side mm(inch)
Pipe Connections Gas Side mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight Body kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L) dB(A)
Power Supply
Ø, V, Hz
Refrigerant Control
Transmission cable
Panel Color
Panel Name(Accessory)
1Way Ceiling Cassette
ARNU07GTU
*4
ARNU09GTU
*4
ARNU12GTU
*4
2.2 2.8 3.6
1,900 2,400 3,100
7,500 9,600 12,300
2.5 3.2 4.0
2,200 2,800 3,400
8,500 10,900 13,600
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
860 x 132 x 450 860 x 132 x 450 860 x 132 x 450
33-27/32 x 5-3/16 x 17-23/32 33-27/32 x 5-3/16 x 17-23/32 33-27/32 x 5-3/16 x 17-23/32
1,100 x 34 x 500 1,100 x 34 x 500 1,100 x 34 x 500
43-5/16 x 1-11/32 x 19-11/16 43-5/16 x 1-11/32 x 19-11/16 43-5/16 x 1-11/32 x 19-11/16
2 x 12 x 18 2 x 12 x 18 2 x 12 x 18
0.16 0.16 0.16
Cross Flow Fan Cross Flow Fan Cross Flow Fan
30 30 30
0.18 0.18 0.18
8.2 / 7.3 / 6.4 9.2 / 8.6 / 8.2 10 / 9.2 / 8.2
289.5 / 257.7 / 225.9 324.7 / 303.6 / 289.5 353 / 324.8 / 289.5
Direct Direct Direct
BLDC BLDC BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene Foamed polystrene
Fuse Fuse Fuse
Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4)
Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2)
25(1) 25(1) 25(1)
13.6(30.0) 13.6(30.0) 13.6(30.0)
32 / 29 / 25 35 / 34 / 32 38 / 35 / 32
1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
1, 220, 60 1, 220, 60 1, 220, 60
EEV EEV EEV
CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Noble White Noble White Noble White
PT-UUC(Grill), PT-UUD(Panel)
Notes:
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics”
chapter should be considered for electrical work and design. Especially the power cable and circuit breaker
should be selected in accordance with that.
5. EEV: Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
* Model Name
A:Basic, C:Plasma