Indoor unit
Ceiling Cassette 4-way(2)
_
19
Indoor Units
10. Installation
10.2 Ceiling opening dimensions and hanging bolt location
Ceiling board
Level gauge
Ceiling
TM/TN Chassis
Unit:mm
875(Ceiling opening)
787(Hanging bolt)
684(Hanging bolt)
671
875(Ceiling opening)
840 Unit size
840 Unit size
• The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions.
• Select and mark the position for fixing bolts and pip-
ing hole.
• Decide the position for fixing bolts slightly tilted to
the drain direction after considering the direction of
drain hose.
• Drill the hole for anchor bolt on the wall.
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to
damage electric wires.
CAUTION
Ceiling
Ceiling Board
Ceiling Board
Floor
Unit:mm(inch)
At least 1800(70-7/8)
4200(165-1
1/32) or less
1000(39-3/8)
or more
10(13/32)
or more
500(19-11/16)
or more
15(19/32)
±3(1/8)
500(19-11/16)
or more
300(1
1-
13
/16) or less
n
TM/TN Chassis
Содержание ARNU48GBRZ4