Indoor unit
Ceiling Cassette 4-way(2)
_
11
Indoor Units
6. Capacity Tables
Heating capacity
Notes:
TC: Total Capacity(kW)
1. Capacity tables show the representative value of conditions which may occur.
2.
is shown as reference. When selecting the outdoor units, avoid the
outdoor air temperature range shown by
.
3. In accordance with operation limits of outdoor unit, applicable range of
capacity tables is different.
4. Refer to Capacity Correction Factor in the outdoor unit PDB for the actual
performance data of each indoor unit and outdoor unit combination.
Capacity
Index
Outdoor air
temp.
DB(°C) WB(°C)
Indoor air temp. (DB, °C)
16 18 20 21 22 24
TC TC TC TC TC TC
kW kW kW kW kW kW
-24.8 -25.0 4.6 4.6 4.6 4.6 4.6 4.6
-21.8 -22.0 5.6 5.6 5.6 5.6 5.6 5.5
-19.8 -20.0 5.9 5.9 5.9 5.9 5.9 5.8
-18.8 -19.0 6.0 6.0 6.0 6.0 6.0 6.0
-16.7 -17.0 6.3 6.3 6.3 6.3 6.3 6.3
-14.7 -15.0 6.6 6.6 6.6 6.6 6.6 6.6
-12.6 -13.0 6.9 6.9 6.9 6.9 6.9 6.9
-10.5 -11.0 7.2 7.2 7.2 7.2 7.2 7.0
-9.5 -10.0 7.4 7.4 7.3 7.3 7.3 7.0
-8.5 -9.1 7.5 7.5 7.5 7.5 7.5 7.0
-7.0 -7.6 7.7 7.7 7.7 7.7 7.5 7.0
-5.0 -5.6 8.0 8.0 8.0 7.7 7.5 7.0
-3.0 -3.7 8.4 8.2 8.0 7.7 7.5 7.0
0.0 -0.7 8.6 8.3 8.0 7.7 7.5 7.0
3.0 2.2 8.8 8.5 8.0 7.7 7.5 7.0
5.0 4.1 8.9 8.5 8.0 7.7 7.5 7.0
7.0 6.0 9.0 8.5 8.0 7.7 7.5 7.0
9.0 7.9 9.0 8.5 8.0 7.7 7.5 7.0
11.0 9.8 9.0 8.5 8.0 7.7 7.5 7.0
13.0 11.8 9.0 8.5 8.0 7.7 7.5 7.0
15.0 13.7 9.0 8.5 8.0 7.7 7.5 7.0