User manual of EL8-EC***F AC Servo
99
External brake released
BRK-OFF
03h
83h
Positioning completed
INP
04h
84h
At-speed
AT-SPEED
05h
85h
Torque limit signal
TLC
06h
86h
Zero speed clamp detection
ZSP
07h
87h
Velocity coincidence
V-COIN
08h
88h
Position command ON/OFF
P-CMD
0Bh
8Bh
Velocity limit signal
V-LIMIT
0Dh
8Dh
Velocity command ON/OFF
V-CMD
0Fh
8Fh
Servo status
SRV-ST
12h
92h
Homing done
HOME-OK
22h
A2h
Position comparison
CMP-OUT
14h
94h
Please don’t set any other than the outputs listed in the table above.
·
Normally open
:
Active low
·
Normally close
:
Active high
·
Front panel is of hexadecimal system.
·
Pr4.10 – Pr4.12 corresponds to DO1 – DO3. If all parameters are set to 0, master device
controls the outputs, object dictionary 0x60FE sub-index 01 bit16-18 corresponds to DO1-DO3.
Pr4.22
Label
Analog input 1 zero drift
Mode
F
Range
-32766~3276
6
Unit 0.3mv Default
0
Index
2422h
Activation
Immediate
To set zero drift compensation value for zero drift correction.
Pr4.23
Label
Analog input 1 filter
Mode
F
Range
0~6400
Unit
0.01m
s
Default
0
Index
2423h
Activation
Immediate
To set a delay filter time coefficient for AI1 input voltage. When filter time takes effect, input
voltage will be smoothen.
Pr4.24
Label
Analog input 1 overvoltage
Mode
F
Range
0~100
Unit 0.1V Default
0
Index
2424h
Activation
Immediate
When Pr4.23 = 0, Pr4.23 invalid. Er270 might occur when the input voltage of AI1 is higher than
the voltage after zero drift correction.
Pr4.25
Label
Analog input 2 zero drift
Mode
F
Range
-32766-32766 Unit
-
Default
1
Index
2425h
Activation
Immediate
To set zero drift compensation value for zero drift correction.
Pr4.26
Label
Analog input 2 filter
Mode
F
Range
0~6400
Unit
-
Default
1
Index
2426h
Activation
Immediate
To set a delay filter time coefficient for AI1 input voltage. When filter time takes effect, input
voltage will be smoothen.