Handbook OPTIFLEX 1300 C
57 OPTIFLEX
1300
C
Function (Fct.)
Input Range
Description
C.1.15.0 Gas
ε
r
0.8 to 115.
1
A major parameter for TDR level
measurement devices. This manually sets
the
ε
r
value of the air/gas inside the tank.
C.1.16.0 Level threshold
7 Gains, 0 to +1.25V.
Dependant on Gain
Enables distinction between disturbances
in the measurement signal and the actual
level signal. Refer to section 4.2.4 further
information.
C.1.17.0 Interface threshold
7 Gains, 0 to +1.25V.
Dependant on Gain
Enables distinction between disturbances
in the measurement signal and the actual
interface signal. Refer to section 4.2.4 for
further information.
C.1.18.0 Probe end threshold
7 Gains, 0 to +1.25V or -
1.25 to 0V (depending on
probe end pulse polarity
in service menu item
D.1.10.0).
Dependant on Gain
Enables distinction between disturbances
in the measurement signal and the actual
probe end signal. Refer to section 4.2.4
for further information.
C.1.19.0 Units for tables
The device can perform volume and
mass conversion operations by pairing
values in a table. The units for the table
columns can be picked from the lists
here.
C.1.19.1 Length unit
m, cm, mm, inch, ft,
ft+inch+1/18inch,
ft+inch+1/32inch or free
unit.
m
Pick the length unit to be used in
volume/mass conversion table from the
list. If free unit is selected, the unit given in
item C.5.1.7 is used.
C.1.19.2 Conversion unit
m³, L, US gal, GB gal, ft³,
bbl, Tons, kg, US tons,
GB tons or free unit.
m³
Pick the conversion unit to be used in the
conversion table from the list. If a mass
conversion unit is directly selected here, a
mass conversion table will be created
(volume conversion will then not be
possible). If free unit is selected, the unit
given in item C.5.1.9 is used.
C.1.20.0 Product density
0 to 9999.99 kg/m³.
0
A volume conversion table together with a
product density greater than 0, could be
used to calculate mass. If a mass
conversion unit has already been directly
selected, this menu is disabled.
C.1.21.0 Volume/Mass table
Level: 0 m or 0 ft to tank
height (C.1.2.0)+tank
bottom offset
(C.1.11.0)+reference
offset (C.1.10.0); volume:
0 m³ to tank volume.;
mass: 0 kg to mass of full
tank.
Give number of value pairs needed. Enter
the length and corresponding volume/
mass values. 50 pairs maximum.
C.1.22.0 Linearization table
0 m or 0 ft to tank height
(C.1.2.0)+tank bottom
offset
(C.1.11.0)+reference
offset (C.1.10.0).
Can increase accuracy via on-site
calibration. Give the number of value pairs
needed. Use an accurate alternative
method of measurement to give a
corrective value to a given measurement.
50 pairs maximum.
C.2.0.0 I/O
For Fieldbus
Not yet available.
C.3.0.0 Output
1(HART)
Defines characteristics of output 1.
Содержание optiplex 1300 c
Страница 1: ......
Страница 49: ...Handbook OPTIFLEX 1300 C 49 OPTIFLEX 1300 C 1 Volume measurement of liquids...
Страница 50: ...Handbook OPTIFLEX 1300 C OPTIFLEX 1300 C 50 2 Volume measurement of solids...
Страница 51: ...Handbook OPTIFLEX 1300 C 51 OPTIFLEX 1300 C 3 Mass measurement of liquids or solids...
Страница 62: ...Handbook OPTIFLEX 1300 C OPTIFLEX 1300 C 62 Finding the advanced setup menu...
Страница 95: ...Handbook OPTIFLEX 1300 C 95 OPTIFLEX 1300 C Note...