10.4.1 Option K1
Air-cooling maintenance
Material Compressed air for blowing out
Cleaning cloths
Vacuum cleaner
Spare parts as required
Precondition The power supply disconnecting device is switched off,
lock out / tag out the device,
the absence of voltage has been verified.
Fig. 31 Clean the refrigerant condenser
1
Refrigerant condenser
2
Maintenance opening
1. Use compressed air to blow the refrigerant condenser clean at regular intervals.
2. Have stubborn clogging removed by an authorized KAESER service representative.
10.4.2 Option K2
Water-cooling maintenance
A clogged refrigerant condenser and dirt trap cause the condensation temperature to rise.
➤ Monitor the condensation temperature to detect any tendency to rise.
Check the refrigerant condenser and dirt trap regularly for leaks and contamination. Frequency of
checking is dependent on the characteristics of the cooling water.
Precondition The power supply disconnecting device is switched off,
lock out / tag out the device,
the absence of any voltage has been verified.
Checking for leaks
1. Check the condenser for visible leaks.
2. Have an authorized KAESER service representative check the condenser for internal leaks at
least once a year.
10 Maintenance
10.4 Cleaning the refrigerant condenser
No.: 901760 02 USE
Operator Manual Refrigerated Dryer
TG
61
Содержание TG 450
Страница 2: ...Original instructions KKW DTG 2 02 en Z1 SBA TROCKNER 20221118 115620...
Страница 6: ...Contents iv Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 8: ...List of Illustrations vi Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 10: ...List of Tables viii Operator Manual Refrigerated Dryer TG No 901760 02 USE...