■ Activate/deactivate automatic restart after a power failure:
■ Activate/deactivate the «Remote control» key
4.8.6.3 Screen 3
Use «DOWN» to open the next screen.
Fig. 16 Information: Screen 3
1
Units of measure used (here: °C)
2
Installation altitude (here: 500 m)
3
Condensate drain: Activate fault message
(here: Fault message activated)
4
Electric energy saved with "eco" operation
You can change the following settings in this screen:
■ Setting the unit of measurement:
─ Parameter °C: Temperature in “°C”, pressure in “bar” and length in “m”
─ Parameter °F: Temperature in “°F”, pressure in “psi” and length in “feet”
■ Adjust installation altitude:
─ Adjustment range: 0 m to 4000 m (default setting 500 m)
─ Above 1000 m the altitude setting must always be adjusted.
■ Activate or deactivate fault message:
In the delivery condition a fault message is output at the condensate drain in the event of a
fault. The refrigeration dryer continues running.
If you activate the fault message, the control additionally reports a fault. This is only output if
the condensate drain was malfunctioning for the duration of 10 min without interruption. The
refrigerated dryer switches off.
4.8.7 Service menu
Use the «UP» or «DOWN» keys to select the
<Service>
menu. This menu may consist of several
screens.
Press «Enter» to open the first screen.
Screen 1: Condensate drain
It is not possible to change the start value.
4
Design and Function
4.8
SIGMA CONTROL SMART
No.: 901760 02 USE
Operator Manual Refrigerated Dryer
TG
33
Содержание TG 450
Страница 2: ...Original instructions KKW DTG 2 02 en Z1 SBA TROCKNER 20221118 115620...
Страница 6: ...Contents iv Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 8: ...List of Illustrations vi Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 10: ...List of Tables viii Operator Manual Refrigerated Dryer TG No 901760 02 USE...