7.2 Instructions to be observed before commissioning or re-commis‐
sioning
Incorrect or improper commissioning can cause injury to persons and damage to the machine.
➤ Commissioning may only be carried out by authorized installation and service personnel who
have been trained on this machine.
Special measures for re-commissioning after storage
Storage period or
standstill longer
than:
Remedy
12 months
➤ Check condensate drainage.
➤ Check the refrigerant condenser.
➤ Check the electrical equipment.
➤ Check all pipes, hoses and fittings for leaks and any visible damage. Cor‐
rect any defects immediately.
36 months
➤ Have the overall technical condition checked by an authorized KAESER
service representative.
Tab. 30 Re-commissioning after storage
7.3 Checking installation and operating conditions
➤ Check and confirm all the items of the checklist before commissioning the machine:
To be checked
See
chapter
Confirmed?
➤ Are operating personnel completely familiar with the applicable safe‐
ty regulations?
–
➤ Have all of the installation conditions been fulfilled?
➤ Are the tolerance limits of the power supply within the permissible
tolerance limits of the rated machine voltage?
(see electrical diagrams)
➤ Are the power supply cable conductor cross-sections and fuse rat‐
ings adequate?
➤ Have all electrical connections been checked for tightness?
–
➤ Has a safety relief valve been installed by the user?
➤ Shut-off valves fitted to the compressed air connections?
➤ Supply of cooling water ensured? (Option K2)
➤ Is the condensate drain connected?
➤ Option H1: Is the machine firmly anchored to the floor?
➤ Installation altitude >3000 ft:
Has the manufacturer been consulted?
Have the controller parameters been adjusted?
7
Initial Start-up
7.2
Instructions to be observed before commissioning or re-commissioning
No.: 901760 02 USE
Operator Manual Refrigerated Dryer
TG
49
Содержание TG 450
Страница 2: ...Original instructions KKW DTG 2 02 en Z1 SBA TROCKNER 20221118 115620...
Страница 6: ...Contents iv Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 8: ...List of Illustrations vi Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 10: ...List of Tables viii Operator Manual Refrigerated Dryer TG No 901760 02 USE...