Fig. 20 Operating elements, displays and connections of the communications module
Item Designation
Color
Status
Description
X1
–
–
Supply voltage: 24 VDC
X2
–
–
CAN, 9-pole sub D plug
X3
–
–
Ethernet, RJ45 socket
1
SYS
LED
system status
Green
on
Standard operation, firmware started
Yellow
on
Transition state
Yellow/
green
flashes
Activating the communications module is
in progress
–
off
No supply voltage
2
COM
LED
communication
Green
on
Standard operation, CAN and Ethernet
communication running
–
off
RESET button pressed
Red
flashes
1x/s
CAN communication malfunction / Ether‐
net communication running
Red
flashes
2x/s
Ethernet communication malfunction /
CAN communication running
3
Ethernet LINK LED
Green
off
No connection
on
Connection established
4
Ethernet ACT LED
Yellow
off
No Ethernet communication
flashes
Ethernet communication running
5
–
–
–
Pin 1
6
RESET key in housing
underneath opening
–
–
Pressing the key with a suitable object for
more than 3 s will reset the IP settings (IP
address, SubNetMask, Gateway) to the
factory setting
Tab. 26 Plug-in communications module – operating elements, displays and connections
4
Design and Function
4.9
MODBUS TCP communication module
36
Operator Manual Refrigerated Dryer
TG
No.: 901760 02 USE
Содержание TG 450
Страница 2: ...Original instructions KKW DTG 2 02 en Z1 SBA TROCKNER 20221118 115620...
Страница 6: ...Contents iv Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 8: ...List of Illustrations vi Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 10: ...List of Tables viii Operator Manual Refrigerated Dryer TG No 901760 02 USE...