Item Name
Function
12
Warning/
Maintenance
Continuous yellow light indicates a warning or maintenance message.
13
Remote control
Continuous yellow light when remote control is activated.
14
ON
Lights green when the machine is switched on.
15
Dew point
Indicates the dew point progress (trend display):
■ Blue: Pressure dew point too low
■ Green: Optimal pressure dew point
■ Yellow: Pressure dew point rising
■ Red: High pressure dew point (message contact switches)
eco
Energy-saving operation
16 Indicates messages
concerning individual
components
From left to right:
■ Refrigerant compressor
■ Refrigerant condenser
■ Condensate drain
■ Safety pressure monitor
■ Machine sensors
─ Temperature transducer
─ Pressure transducer
Tab. 22 Indicators
4.8.2 User operation SIGMA CONTROL SMART
Handling concept
Task
Procedure
Navigating
the menu
For navigating the menus, a cursor is provided to move the «UP» and «DOWN»
keys The current cursor position is indicated by inverse coloring.
Use the «Enter» key to switch, for example, from the main menu into a sub-menu. If
a single menu is too large, the information is provided in several numbered screens
(images). The corresponding symbol in the Main menu appears somewhat darker in
this case.
Changing
parameters
To change parameters, navigate to an entry and confirm with «Enter».
This enables you to use the «UP» and «DOWN» keys to change values or activate/
deactivate check boxes:
■ Check box activated: ✓
■ Check box deactivated: ☐
Confirm your selection with «Enter». The change is now active.
Tab. 23 Handling concept
4
Design and Function
4.8
SIGMA CONTROL SMART
28
Operator Manual Refrigerated Dryer
TG
No.: 901760 02 USE
Содержание TG 450
Страница 2: ...Original instructions KKW DTG 2 02 en Z1 SBA TROCKNER 20221118 115620...
Страница 6: ...Contents iv Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 8: ...List of Illustrations vi Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 10: ...List of Tables viii Operator Manual Refrigerated Dryer TG No 901760 02 USE...