2.6 Refrigerant circuit
The refrigerated dryer contains a refrigerant that is classified as a fluorinated global warming gas.
This refrigerant is required for the function of the machine.
TG 450
TG 520
TG 650
TG 780
TG 980
Refrigerant
R-513A
R-513A
R-513A
R-513A
R-513A
Global warming potential
(GWP)
631
631
631
631
631
Charge quantity
1)
[lb]
9.48
9.04
2)
9.59
8.82
2)
14.11
13.45
2)
13.23
12.57
2)
17.42
17.20
2)
Charge quantity as CO
2
equivalent [t]
2.71
2.59
2)
2.74
2.52
2)
4.04
3.85
2)
3.79
3.60
2)
4.98
4.92
2)
Maximum working pres‐
sure [psig] (high pressure
end)
348
348
348
348
348
Maximum working pres‐
sure [psig] (low pressure
end)
305
305
305
305
305
Pressure monitor:
Cut-out pressure [psig]
334
334
334
334
334
1)
Volume of fluorinated global warming gases for which the refrigerant system was designed
2)
Option K2
Tab. 8 Refrigerant circuit
2.7 MODBUS TCP communications module
Communication interface
Characteristic
Value
Communication bus
SIGMA NETWORK / MODBUS TCP server
(slave)
SIGMA NETWORK cable
CAT5, 2x2x0.64, color grey (meter goods)
Material number: 7.9679.0
Retrofit Kit
SCS RJ45 connector plug (RJ45 plug, 90° off‐
set, 4 displacement/clamping contacts, tool-free
installation (Fast Connect))
Material number: 7.5250.02180
MODBUS TCP cable
CAT5 shielded, copper, color green (meter
goods)
Material number: 7.7629.0
Power supply [V DC]
24
Transfer rate [Mbit/s]
10/100
Properties 1
Auto crossing (Auto-MDI (X))
Properties 2
Auto negotiation
2
Technical Data
2.6
Refrigerant circuit
No.: 901760 02 USE
Operator Manual Refrigerated Dryer
TG
7
Содержание TG 450
Страница 2: ...Original instructions KKW DTG 2 02 en Z1 SBA TROCKNER 20221118 115620...
Страница 6: ...Contents iv Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 8: ...List of Illustrations vi Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 10: ...List of Tables viii Operator Manual Refrigerated Dryer TG No 901760 02 USE...