2.8.1 Option K2
Water-cooling
The primary side of the heat exchanger is connected to the machine. The specifications refer
to the secondary side of the heat exchanger.
2.8.1.1 Design data for the cooling system
TG 450
TG 520
TG 650
TG 780
TG 980
Inlet temperature
1)
[°F]
84
84
84
84
84
Cooling water tempera‐
ture rise
1)
[F]
17
18
14
12
17
Flow rate
1)
[gpm]
7.18
7.44
11.22
16.20
17.35
Pressure drop
1)
[psi]
6.5
7.1
4.5
8.7
10.2
1)
ISO 7183 Option A2:
■ Reference point: 14.5 psi(a), 68 °F, 0 % relative humidity:
■ Operating point: Working pressure 100 psig, compressed air inlet temperature 100 °F,
100 % relative humidity
Tab. 10 Design data for the cooling system
2.8.1.2 Component specification:
Feature
Value
Material (Heat exchang‐
er)
1.4401
Solder (Heat exchanger)
Copper (Cu)
Max. working pres‐
sure [psig]
145
Max. permissible pres‐
sure differential with
closed valves [psi]
50
Minimum permissible in‐
let temperature [°F]
40
Max. permissible inlet
temperature* [°F]
104
Unsuitable cooling media
Salt water
Consult an authorized KAESER service representative on the suitabili‐
ty of cooling water solutions.
* Contact an authorized KAESER service representative regarding higher values.
Tab. 11 Component specifications (Option K2)
2
Technical Data
2.8
Water Cooling
No.: 901760 02 USE
Operator Manual Refrigerated Dryer
TG
9
Содержание TG 450
Страница 2: ...Original instructions KKW DTG 2 02 en Z1 SBA TROCKNER 20221118 115620...
Страница 6: ...Contents iv Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 8: ...List of Illustrations vi Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 10: ...List of Tables viii Operator Manual Refrigerated Dryer TG No 901760 02 USE...