6.4 Connecting the condensate drain
A threaded hose connection is provided to attach a condensate drain hose.
The condensate must be able to drain freely.
➤ Only machines with 232 psig maximum permissible working pressure may be connected
to the condensate collecting line.
Fig. 25 illustrates the recommended installation.
Condensate flows downward into the condensate collecting line. This prevents condensate flowing
back to the machine.
During summer operation and increased ambient temperatures, this can lead to dew forma‐
tion and the formation of condensate on the condensate lines.
➤ The condensate lines must be insulated accordingly.
If condensate flows at several points into the condensate collecting line, you must install shut-off
valves in the condensate lines to shut the condensate line off before commencing maintenance
work.
Condensate line
Feature
Value
Max. length
1)
[ft]
49
Max. delivery head [ft]
16
Material
(pressure-resistant, cor‐
rosion-proof)
Copper
Stainless steel
Plastics
Hose line
1)
For longer lengths, please contact an authorized KAESER service representative before instal‐
lation.
Tab. 27 Condensate line
Condensate collecting line
Feature
Value
Gradient [%]
>1
Max. length
1)
[ft]
66
Material
(pressure-resistant, cor‐
rosion-proof)
Copper
Stainless steel
Plastic
Hose line
1)
For longer lengths, please contact an authorized KAESER service representative before instal‐
lation.
Tab. 28 Condensate collecting line
6
Installation
6.4
Connecting the condensate drain
44
Operator Manual Refrigerated Dryer
TG
No.: 901760 02 USE
Содержание TG 450
Страница 2: ...Original instructions KKW DTG 2 02 en Z1 SBA TROCKNER 20221118 115620...
Страница 6: ...Contents iv Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 8: ...List of Illustrations vi Operator Manual Refrigerated Dryer TG No 901760 02 USE...
Страница 10: ...List of Tables viii Operator Manual Refrigerated Dryer TG No 901760 02 USE...