Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-83-
Function
code
Name
Description
Default
value
PROFIBUS/CANopen/DeviceNet (0
–
1000)
17: Value 2 set through
PROFIBUS/CANopen/DeviceNet (0
–
1000)
18: Value 1 set through Ethernet 1 (0
–
1000)
19: Value 2 set through Ethernet 2 (0
–
1000)
20: HDIB input (0.00
–50.00kHz)
21: Value 1 set through
EtherCAT/Profinet/Ethernet IP (0
–1000)
22: Torque current (bipolar, 0
–Triple the
motor rated current)
23: Exciting current (bipolar, 0
–Triple the
motor rated current)
24: Set frequency (bipolar, 0
–Max. output
frequency)
25: Ramp reference frequency (bipolar,
0
–Max. output frequency)
26: Rotational speed (bipolar, 0
–Speed
corresponding to max. output frequency)
27: Value 2 set through
EtherCAT/Profinet/Ethernet IP (0
–1000)
28: AO1 from the Programmable card (0
–
1000)
29: AO2 from the Programmable card (0
–
1000)30: Rotational speed (0
–Twice the
motor rated synchronous speed)
31: Output torque (Actual value, 0
–Twice
the motor rated torque)
32: AI/AO temperature detection output
33
–63: Reserved
P06.17
Lower limit of AO1 output
-300.0%
–P06.19
0.0%
P06.18
Corresponding AO1 output of
lower limit
0.00V
–10.00V
0.00V
P06.19
Upper limit of AO1 output
P06.17
–300.0%
100.0%
P06.20
Corresponding AO1 output of
upper limit
0.00V
–10.00V
10.00V
P06.21
AO1 output filter time
0.000s
–10.000s
0.000s
P06.22
–
P06.26
Reserved
/
/
P06.27
Lower limit of HDO output
-300.0%
–P06.29
0.0%
P06.28
Corresponding HDO output of
lower limit
0.00
–50.00kHz
0.0kHz
P06.29
Upper limit of HDO output
P06.27
–300.0%
100.0%
Содержание GD350-004G/5R5P-45-AS
Страница 1: ...Goodrive350 IP55 High ingress Protection Series VFD ...