Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-180-
Function
code
Name
Description
Default
value
Modify
than that of output frequency, if no measures are
taken, the VFD may trip due to overcurrent during
acceleration.
0x00
–0x11
Ones: Current-limit action selection
0: Invalid
1: Always valid
Tens: Hardware current-limit overload alarm
selection
0: Valid
1: Invalid
P11.06
Automatic
current-limit
level
Current-limit protection function detects output
current during running, and compares it with the
current-limit level defined by
, if it exceeds
the current-limit level, the VFD will run at stable
frequency during accelerated running, or run in
decreased
frequency
during
constant-speed
running; if it exceeds the current-limit level
continuously, the VFD output frequency will drop
continuously until reaching lower limit frequency.
When the output current is detected to be lower
than the current-limit level again, it will continue
accelerated running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
Setting range of
: 50.0
–200.0% (of the rated
VFD output current)
Setting range of
: 0.00
–50.00Hz/s
G model:
160.0%
P model:
120.0%
◎
P11.07
Frequency-dro
p rate during
current limit
10.00
Hz/s
◎
P11.08
VFD or motor
overload/unde
rload
pre-alarm
0x0000
–0x1132
Ones place:
0: Motor overload/underload pre-alarm, relative to
rated motor current
1: VFD overload/underload pre-alarm, relative to
rated VFD output current
2: VFD output torque overload/underload
pre-alarm, relative to rated motor torque
Tens place:
0: The VFD continues running after
overload/underload alarm.
1: The VFD continues running after underload
0x0000
○