Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-140-
Function
code
Name
Description
Default
value
Modify
P03.35
Control
optimization
setting
0
–0x1111
Ones place: Torque command selection
0: Torque reference
1: Torque current reference
Tens place: Reserved
0: Reserved
1: Reserved
Hundreds place: Whether to enable ASR
integral separation
0: Disable
1: Enable
Thousands place: Reserved
0: Reserved
1: Reserved
0x0000
○
P03.36
Speed loop
differential gain
0.00
–10.00s
0.00s
○
P03.37
High-frequency
current loop
proportional
coefficient
Under closed-loop vector control mode
(
, the current loop PI
parameters are
; above
and
Setting range of
: 0
–65535
Setting range of
: 0
–65535
Setting range of
: 0.0
–100.0% (relative to
max. frequency)
1000
○
P03.38
High-frequency
current loop
integral
coefficient
1000
○
P03.39
Current loop
high-frequency
switch-over point
100.0%
○
P03.40
Inertia
compensation
enable
0: Disable
1: Enable
0
○
P03.41
Upper limit of
inertia
compensation
torque
Limit the max. inertia compensation torque to
prevent inertia compensation torque from being
too large.
Setting range: 0.0
–150.0% (rated motor torque)
10.0%
○
P03.42
Inertia
compensation
filter times
Filter times of inertia compensation torque, used
to smooth inertia compensation torque.
Setting range: 0
–10
7
○
P03.43
Inertia
identification
torque value
Due to friction force, it is required to set certain
identification torque for the inertia identification
to be performed properly.
0.0
–100.0% (rated motor torque)
10.0%
○
P03.44
Enable inertia
identification
0: No operation
1: Start identification
0
◎
P03.45
Current loop
proportional
Automatic update will be performed after motor
parameter autotuning. In the closed-loop vector
0
●