Goodrive350 IP55 High-ingress Protection Series VFD
Troubleshooting
-254-
Fault
code
Fault type
Possible cause
Corrective measures
SECAN
[58] CAN master/slave
communication card
communication timeout fault
There
is
no
data
transmission between the
CAN master and slave
communication cards
Check
whether
the
communication card wiring
is loose or dropped
S-Err
[69] CAN slave fault in
master/slave synchronization
Fault occurred to one of
the CAN slave VFDs
Detect the CAN slave VFD
and
analyze
the
corresponding fault cause
of the VFD
P-E1
–
P-E10
[45]
–[54] Programmable card
customized faults 1
–10
User program logic error
in the programmable card.
A fault occurred on the
customized position.
Check the user program
logic.
Perform
troubleshooting
based on actual customized
faults.
OtE1
[70] EC PT100 detected OH
The PT100 temperature
sensor is inaccurate or not
calibrated.
Device
or
ambient
temperature is too high.
Calibrate
the
sensor
through parameter settings.
Lower the device or ambient
temperature.
OtE2
[71] EC PT1000 detected OH
The PT1000 temperature
sensor is inaccurate or not
calibrated.
Device
or
ambient
temperature is too high.
Calibrate
the
sensor
through parameter settings.
Lower the device or ambient
temperature.
E-EIP
[72] EtherNet IP
communication timeout
There
is
no
data
transmission between the
communication card and
the host controller (or
PLC).
Check
whether
the
communication card wiring
is loose or dropped.
E-PAO
[73] No upgrade bootloader
The upgrade bootloader is
missing.
Contact us.
E-AI1
[74] AI1 disconnection
Input voltage of AI1 is too
low;
AI1
wiring
is
disconnected.
Connect a 5V or 10mA
power source to check
whether the input is normal;
Check the wiring or replace
the cables.
E-AI2
[75] AI2 disconnection
Input voltage of AI2 is too
low;
AI2
wiring
is
disconnected.
Connect a 5V or 10mA
power source to check
whether the input is normal;
Check the wiring or replace
the cables.
E-AI3
[76] AI3 disconnection
Input voltage of AI3 is too
low;
AI4
wiring
is
disconnected.
Connect a 5V or 10mA
power source to check
whether the input is normal;
Check the wiring or replace
the cables.