Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-44-
For first power-on, the keypad automatically enters the setup wizard interface. See the
following.
Sure to start the setup wizard?
Set parameters as
prompted.
Present: 0
Auth:
√
0
:简体中文
Default: 0
2
:
Русский язык (Reserve)
3
:
Português (Reserve)
4
:
Español (Reserve)
5
:
Italiano (Reserve)
0: Always
1: Only once
Always: Enable for each power-on
Only once: Disable for next power-on
P00.06: A Freq Cmd
0
:
Set via keypad digits
1
:
Set via AI1
2
:
Set via AI2
3
:
Set via AI3
4
:
Set via high speed pulse HDIA
5
:
Set via simple PLC program
Setup completed.
Present: 0
Auth:
√
Default: 0
Present: 00
Auth:
√
Default: 00
16:02:35 Fwd Local Ready GD350
16:02:35 Fwd Local Ready GD350
Back Home OK
Back Home OK
Back Home Sele
Back Home Sele
Back Home Sele
No Home Yes
1
:
English
16:02:35 Fwd Local Ready GD350
5.5 Basic operation instruction
5.5.1 What this section contains
This section introduces the function modules inside the VFD
Ensure all the terminals are fixed and tightened firmly.
Ensure the motor matches with the VFD power.