Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-46-
The running command channel can be set by terminal commands besides P00.01 and P00.02.
Current running
command
channel
P00.01
Multi-function terminal
function (36)
Command switches to
keypad
Multi-function terminal
function (37)
Command switches to
terminal
Multi-function terminal
function (38)
Command switches to
communication
Keypad
/
Terminal
Communication
Terminal
Keypad
/
Communication
Communication
Keypad
Terminal
/
Note:
"/" means this multi-function terminal is invalid under current reference channel.
Related parameter list:
Function
code
Name
Description
Default
value
P00.00
Speed control mode
0: SVC 0
1: SVC 1
2: SVPWM
3: FVC
Note:
If 0, 1 or 3 is selected, it is required to
carry out motor parameter autotuning first.
2
P00.01
Running command
channel
0: Keypad
1: Terminal
2: Communication
0
P00.02
Communication running
command channel
0: Modbus/Modbus TCP
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFITNET/Ethernet IP
4: PLC programmable card
5: Bluetooth card
6: Reserved
0
P00.15
Motor parameter
autotuning
0: No operation
1: Rotary autotuning 1; carry out
comprehensive motor parameter autotuning;
rotary autotuning is used in cases where high
control precision is required;
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load;
3: Static autotuning 2 (partial autotuning) ;
when current motor is motor 1, only P02.06,
P02.07 and P02.08 will be autotuned; when
current motor is motor 2, only P12.06, P12.07
and P12.08 will be autotuned.
4: Rotary autotuning 2, which is similar to
rotary autotuning 1 but is only applicable to
asynchronous motors.
5: Rotary autotuning 3 (partial autotuning),
which is only applicable to asynchronous
motors.
0