Goodrive350 IP55 High-ingress Protection Series VFD
Communication protocol
-280-
LSB of data
ABH
LSB of CRC CHK
ADH
MSB of CRC CHK
14H
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
9.4.4 Command code: 10H, continuous writing
The command code 10H is used by the master to write data to the VFD. The quantity of data to
be written is determined by "Data quantity", and a maximum of 16 pieces of data can be
written.
For example, to write 5000 (1388H) and 50 (0032H) respectively to 0004H and 0005H of the
VFD whose slave address is 02H, the structure of the frame is described in the following table.
RTU master command (transmitted by the master to the VFD)
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
02H
CMD
10H
MSB of data writing address
00H
LSB of data writing address
04H
MSB of data quantity
00H
LSB of data quantity
02H
Number of bytes
04H
MSB of data to be written to 0004H
13H
LSB of data to be written to 0004H
88H
MSB of data to be written to 0005H
00H
LSB of data to be written to 0005H
32H
LSB of CRC
C5H
MSB of CRC
6EH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
RTU slave response (transmitted by the VFD to the master)
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
02H
CMD
10H
MSB of data writing address
00H
LSB of data writing address
04H
MSB of data quantity
00H
LSB of data quantity
02H
LSB of CRC
C5H
MSB of CRC
6EH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
9.4.5 Data address definition
This section describes the address definition of communication data. The addresses are used
for controlling the running, obtaining the state information, and setting related function
parameters of the VFD.