Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-199-
Function
code
Name
Description
Default
value
Modify
P16.40
Received PZD10 frequency (0–Fmax. Unit: 0.01 Hz)
6: Setting of the upper limit of reverse running
frequency (0
–Fmax. Unit: 0.01 Hz)
7: Upper limit of electromotive torque (0
–
3000, in which 1000 corresponds to 100.0% of
the motor rated current)
8: Upper limit of braking torque (0
–3000, in
which 1000 corresponds to 100% of the motor
rated current)
9: Virtual input terminal command (Range:
0x000
–0x3FF, corresponding to
S8/S7/S6/S5/HDIB/HDIA/S4/S3/S2/S1)
10: Virtual output terminal command (Range:
0x00
–0x0F, corresponding to
RO2/RO1/HDO/Y1)
11: Voltage setting (special for V/F separation)
(0
–1000, in which 1000 corresponds to
100% of the motor rated voltage)
12: AO1 output setting 1 (-1000
–+1000, in
which 1000 corresponds to 100.0%)
13: AO2 output setting 2 (-1000
–1000, in
which 1000 corresponds to 100.0%)
14: High-order bit of position reference
(signed)
15: Low-order bit of position reference
(unsigned)
16: High-order bit of position feedback
(signed)
17: Low-order bit of position feedback
(unsigned)
18: Position feedback setting flag (position
feedback can be set only after this flag is set
to 1 and then to 0)
19: Function parameter mapping (PZD2
–
PZD12 correspond to P14.49
–P14.59)
20
–31: Reserved
0
○
P16.41
Received PZD11
0
○
P16.42
Received PZD12
0
○
P16.43
Sent PZD2
0
–31
0: Invalid
1: Running frequency (x100, Hz)
2: Set frequency (x100, Hz)
3: Bus voltage (x10, V)
4: Output voltage (x1, V)
5: Output current (x10, A)
6: Actual output torque (x10, %)
7: Actual output power (x10, %)
8: Rotation speed of running (x1, RPM)
0
○
P16.44
Sent PZD3
0
○
P16.45
Sent PZD4
0
○
P16.46
Sent PZD5
0
○
P16.47
Sent PZD6
0
○
P16.48
Sent PZD7
0
○
P16.49
Sent PZD8
0
○