Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-147-
Function
code
Name
Description
Default
value
Modify
P04.44
Starting
frequency point
for switching off
IF mode for
asynchronous
motor 1
0.00
–P04.50
10.00Hz
○
P04.45
Enable/disable
IF mode of
asynchronous
motor 2
0: Disabled
1: Enabled
0
◎
P04.46
IF current setting
of asynchronous
motor 2
When IF control is adopted for asynchronous
motor 2, this parameter is used to set the output
current. The value is a percentage in relative to
the rated current of the motor.
Setting range: 0.0
–200.0%
120.0%
○
P04.47
IF proportional
coefficient of
asynchronous
motor 2
When IF control is adopted for asynchronous
motor 2, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
Setting range: 0
–5000
650
○
P04.48
IF integral
coefficient of
asynchronous
motor 2
When IF control is adopted for asynchronous
motor 2, this parameter is used to set the
integral coefficient of the output current
closed-loop control.
Setting range: 0
–5000
350
○
P04.49
Starting
frequency point
for switching off
IF mode for
asynchronous
motor 2
0.00
–P04.51
10.00Hz
○
P04.50
End frequency
point for
switching off IF
mode for
asynchronous
motor 1
P04.44
–P00.03
25.00Hz
○
P04.51
End frequency
point for
switching off IF
mode for
asynchronous
motor 2
P04.49
–P00.03
25.00Hz
○